Specifications
Â
5 Year Warranty |
 |
Approvals:Â Â |
Â
Single Output |
||||
Model Number |
Output Voltage |
Max. Output Current |
Total Regulation |
Max. Output Power |
SIUA300-S05 |
12 VDC |
23 A |
±5% |
276W |
SIUA300-S08 |
24 VDC |
12.5 A |
±3% |
300W |
SIUA300-S09 |
28~30 VDC |
10.71~10.00 VDC |
±3% |
300W |
SIUA300-S10 |
36 VDC |
8.33 A |
±3% |
300W |
SIUA300-S11 |
48 VDC |
6.25 A |
±2% |
300W |
Â
Electrical Characteristics |
|||||
Parameter |
Test Conditions |
Min. |
Typ. |
Max. |
Unit |
Safety Approvals Input Voltage Range |
Safety Approval & Specification in Label |
100 |
 |
240 |
VAC |
Operate Voltage Range |
 |
90 |
 |
260 |
VAC |
Input Frequency |
Sine wave |
47 |
 |
63 |
Hz |
Power Factor Correction |
lo=Full load, Vin=240AC |
0.95 |
 |
1 |
 |
Output Power Range |
See Rating Chart |
 |
 |
300 |
W |
Low Line Input Current |
Full load, Vin=100VAC |
 |
3.9 |
 |
A |
High Line Input Current |
Full load, Vin=240VAC |
 |
1.6 |
 |
A |
Low Line Input Inrush Current |
Full load, 25°C, Cool start, Vin=100VAC |
 |
 |
45 |
A |
High Line Input Inrush Current |
Full load, 25°C, Cool start, Vin=240VAC |
 |
 |
108 |
A |
Safety Ground Leakage Current |
Vin=240VAC, Fi=60Hz |
 |
 |
0.75 |
mA |
Efficiency |
Full Load, Vin=230VAC |
87 |
 |
92 |
% |
Line Regulation |
Full Load, Vin=100~120VAC |
0.5 |
 |
1 |
% |
Load Regulation |
Vin=230VAC, 10~90% Load Change at Condition |
2 |
 |
5 |
% |
Over Voltage Protection |
Over Voltage Protection |
112 |
 |
132 |
% |
Over Load Protection |
Recovers automatically after fault condition is removed |
110 |
 |
150 |
% |
Time of Transient Response |
Io=Full Load to Half Load, Vin=110VAC |
 |
 |
4 |
ms |
Hold-Up Time |
Full Load, Vin=100VAC |
 |
 |
20 |
ms |
Start Up Time |
Full Load, Vin=100~240VAC |
 |
 |
3 |
s |
Ripple & Noise (Peak to Peak) |
 |
 |
 |
1 |
% |
Temperature Coefficient |
Full Load, Vin=100~240VAC |
 |
 |
±0.04 |
%/°C |
Dielectric Withstanding Voltage(P-S) |
Primary to Secondary |
 |
 |
4242 |
VDC |
Dielectric Withstanding Voltage(P-G) |
Primary to PE |
 |
 |
2121 |
VDC |
EMC Emission |
Compliance to EN55022(CISPR22) |
 |
 |
B |
Class |
Â
Â
Environmental |
|||||
Parameter |
Test Conditions |
Min. |
Typ. |
Max. |
Unit |
Operating Temperature |
Derate linearly from 100% load at 50â to 50% load at 70â |
-20 |
 |
70 |
°C |
Storage Temperature |
 10~95% RH |
-40 |
 |
85 |
°C |
Operating Humidity |
 non-condensing |
0 |
 |
95% |
RH |
Storage Humidity |
 |
0 |
 |
95% |
RH |
Electro Static Discharge |
Air Discharge, IEC61000-4-2 |
 |
 |
8 |
KV |
Electro Static Discharge |
Contact Discharge, IEC61000-4-2 |
 |
 |
4 |
KV |
Mean Time Between Failure |
Operation Temperature at 25â, Calculated per MIL-HDBK-217F |
100K |
 |
 |
h |
Operating Altitude (Elevation) |
All Condition |
 |
 |
2000 |
m |
Vibration |
10~500Hz,10min./1cycle, 60min.each along X, Y, Z axes |
 |
 |
5 |
G |
Surge Voltage |
 Line-Neutral |
 |
 |
1 |
KV |
Surge Voltage |
 Line-PE & Neutral-PE |
 |
 |
2 |
KV |
Â
Mechanical Diagram |
PIN CHART
Â
|
Note: 1. Dimensions are shown in mm. 2. Weight: 790gs  approx. 3. Input connector mates with DINKLE#DT-2GN-B01W-02P  4. Output connector mates with DINKLE#DT-2GN-B01W-(04P or 06P)  |
||||||||||||||||||||||||
Derating Curve |
1. Operating Temperature: -20 to 70°C 2. Derate linearly from 100% load at 50°C to 50% load at 70°C |
Â
Datasheet PDF
Â
Â