Specifications
Â
3 Year Warranty |
 |
 Approvals: |
Â
Model |
Nominal Input voltage (Vac) |
Output voltage (Vdc) |
Output current (A) |
Efficiency Typ. |
Ripple (mVp-p) |
Certificate |
RIRA180-24 |
100-240Vac |
24 |
7.5 |
90% |
1% Vo |
CE, FCC, CB, UL, CUL |
RIRA180-48 |
48 |
3.8 |
91% |
1% Vo |
CE, FCC, CB, UL, CUL |
1.     The ripple values are measured at 20MHz of bandwidth by using a 12'' twisted pair-wire termin-ated with 0.1uF & 47uF parallel capacitor under ambient temperature 25°C at rated input voltage and rated load;
2.     The efficiency values are measured under ambient temperature 25°C at rated input voltage and rat-ed load.
Â
ELECTRICAL - Input |
PARAMETER |
CONDITIONS |
MIN Â TYP Â MAX |
UNITS |
Input voltage |
 |
90 Â Â Â Â Â Â Â 264 |
Vac |
Input frequency |
 |
47 Â Â Â Â Â Â Â Â 63 |
Hz |
Input current |
Full load, Vin = 115Vac  |
1.8 0.9 |
 A |
Inrush current |
Cold start, Vin = 115Vac Cold start, Vin=230Vac |
35 65 |
A |
|
|||
Power Factor9PF) |
Full load, Vin=115Vac Full load, Vin=230Vac |
0.98 0.96 |
 |
Stand-by power consumption |
Vin=230Vac |
7 |
W |
Surge voltage |
L-N |
2 |
KV |
Â
Â
ELECTRICAL - Output |
PARAMETER |
CONDITIONS |
MIN Â TYP Â MAX |
UNITS |
Output voltage accuracy |
 |
±2 |
% |
 |
RIRA180-24 RIRA180-48 |
21 Â Â -Â Â 28 44 Â - Â 54 |
V Â |
Output voltage adjustment range |
Output voltage can be adjusted within above range by V-ADJ. variable resistance inside of the power supply. When output voltage exceeds the range, the power supply will be in failure or get into over voltage protection mode. To avoid the case that the output voltage is higher than rated voltage, output current should be used under rated current |
||
Minimum load |
 |
0 |
A |
Line regulation |
Vin from 100Vac to 240Vac |
1 |
% |
Load regulation |
Vout from min. to max. |
1 |
% |
Turn-on delay time |
Full load, Vin=115Vac |
3600 |
ms |
Hold up time |
Full load, Vin=115Vac |
20 |
ms |
Â
PROTECTION |
Short circuit |
Hiccup mode, it will recover automatically after fault condition is removed |
Over voltage |
RIRA180-24: over voltage protection value 33VÂ RIRA180-48: over voltage protection value 66V |
|
|
Over current |
RIRA180-24: over current protection value 8.3AÂ RIRA180-48: over current protection value 4.2A |
|
|
Over temperature |
Over temperature protection value: 100±10°C |
|
Â
SAFETY / EMC |
Isolation voltage |
I/P-O/P: 3KVac, I/P-FG: 1.5KVac, O/P-FG: 1.5KVac |
Insulation resistance |
100mQ Max ./500VDC |
Safety |
Design refer to UL60950-1, EN60950-1 |
EMC |
EN 55022:2010+AC:2011 (CISPR 22:2008) ClassB EN 61000-3-2:2014 (IEC 61000-3-2:2014) EN 61000-3-3:2013 (IEC 61000-3-3:2013) EN 55024:2010 (CISPR 24:2010) |
NOTE: Unless otherwise specified, all the above parameters are measured at ambient temperature of 25°C and Vin = 115Vac to 230Vac.Â
Â
Â
ENVIRONMENT |
PARAMETER |
CONDITIONS |
MIN TYP MAX |
UNITS |
Ambient operating temperature |
Startup at rated voltage |
-25 Â Â Â Â +70 |
°C |
Operating relative humidity |
Non condensing |
20 Â Â Â Â Â 95 |
% |
Storage temperature |
Humidity 5 ~ 95% RH |
-40 Â Â Â Â Â +85 |
o |
MTBF |
Full load, 220Vac input, 25°C ambient temperature |
200 |
Khrs |
DC-OK led |
LED(Green) DC OK LED light will be ON when the power supply is properly operated |
||
DC-Low led |
LED(Red) DC Low LED light will be ON: (1) when output voltage is below 85%(±2.5%) from the rated output voltage; (2) when get over voltage, over current, over temperature and short circuit fault |
||
Cooling |
Free air convection |
||
Mounting method |
Vertical |
||
Dimension(W x H x D) |
50.0 x 130.0 x 125.0mm (1.97x5.12x4.92inch) |
||
Weight |
950g |
||
Packing |
13pcs/13.5kg/0.7cuft/carton, Carton size 620 x 260 x 175mm(LxWxH) |